Our strength lies in our proficient team of engineers and dexterous workforce, helps us in manufacturing and exporting Split Phase Inverter 120v-240v dc to ac power inverter. To manufacture this inverter we use optimum quality materials and components, sourced from trusted vendors. Its robust design is suitable for industrial plant environments that have a variety of temperatures, dust, moisture and corrosive contaminants. Split Phase Inverter 120v-240v dc to ac power inverter comes in different technical specifications as per the requirements of clients.
Features:
Split phase 120-240(L1-N 120V, L2-N 120V, L1-L2 240V) Off Grid Inverter
Technical Specification:
Model | SDP 10KW | |||
Isolation mode | Low Frequency Transformer | |||
DC Input | Input rated voltage (Vdc) | 120V | 192V | 240V |
Input rated current(A) | 83.3A | 52A | 41.6A | |
AC Output | Rated output power | 10KW | ||
Output waveform | Pure sine wave | |||
Phases | Two phase 3 wires ground | |||
Output rated voltage | 120/240VAC3%(L1,L2 to N 120V, L1 to L2 240V) | |||
Output Frequency | 50Hz/60Hz 0.05Hz | |||
Power Factor(PF) | 0.9 | |||
Overload Ability | 150%, 10s | |||
Efficiency | 95% | |||
Waveform distortion rate (THD) | <3%(Linear load) | |||
Dynamic Response (0 to 100% load) | 5% 30ms | |||
Display | LCD | |||
Running mode | Working continuously | |||
Electrical insulation properties | 2000Vac, 1 Minute | |||
Protection function | Protection | Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc. | ||
Cooling method | Fan-cooled | |||
Short-circuit protection | No automatic recovery, need to restart the machine | |||
working environment | Ambient temperature | -15 55 | ||
Using environment humidity | 0 90%,No condensation | |||
Noise ( 1 meter) | 50dB | |||
Degree of protection | IP20(indoor) | |||
Using altitude(m) | 2000 | |||
CE Standard | EN60950-1:2006+A11:2009, EN61000-6-4:2007+A1:2001, EN61000-6-2:2005, EN61000-3-12:2005, EN61000-3-11:2000 |