Technical Specification
Model | SDP-80KW | ||
Isolation mode | Low Frequency Transformer | ||
DC Input | Rated voltage (Vdc) | 384V | |
Rated current(A) | 208.3A | ||
AC Output | Rated output power | 80KW | |
Output waveform | Pure Sine Wave | ||
Rated Voltage | 110/220VAC 3% | 380VAC 3% | |
Phases | 2 phase 3 wire | 3 phase 4 wire | |
Rated current (A) | 363.63A (phase current) | 121.2A (phase current) | |
Frequency | 50Hz or 60Hz | ||
Rated output voltage range (V) | 220/230/240/380/400/415/440VAC optional | ||
Phases | Single / Two/ Three phase optional | ||
Power Factor (PF) | >0.95 | ||
Overload Ability | 150%, 5 seconds | ||
Efficiency | >94% | ||
Waveform distortion rate (THD) | <3%(Linear load) | ||
Dynamic Response | 5%, 50ms | ||
Display | LCD | ||
Running mode | Working continuously | ||
Electrical insulation properties | 2000Vac, 1 Minute | ||
AC Bypass Function | Optional | ||
Solar Charge Controller built in | Optional | ||
AC to DC battery Charger built in | Optional | ||
RS485 remote monitoring | Optional | ||
Wide voltage input 100-850VDC(optional) | Off grid inverter can work without battery | ||
Protection Function | Protection | Input reverse polarity, under voltage, overvoltage, | |
Cooling method | Fan-cooled | ||
Short-circuit protection | No automatic recovery, need to restart the machine | ||
Working environment | Noise ( 1 meter) | 50dB | |
Degree of protection | IP20(indoor) | ||
Working Altitude (m) | 2000 | ||
Working temperature | -25 +55 C | ||
relative humidity | 0 90%,non condensing | ||
Mechanical dimension | Depth* Width * Height | 700x750x1400mm | |
Weight (Kg) | 500Kg | ||
Certification | European CE(EMC & LVD), SAA |