Parameters:
| Model | SDP-250KW | |
| Isolation mode | Low Frequency Transformer | |
| DC Input | Rated voltage(Vdc) | 600V |
| Input voltage range(V) | 540-850V | |
| Rated current(A) | 416.7A | |
| AC Output | Rated power(KW) | 250KW |
| Rated voltage | 440VAC3% | |
| Output phases | 3 phase + N + PE | |
| Rated current (A) | 328A (phase current) | |
| Output frequency | 50Hz or 60Hz | |
| Output waveform | Pure Sine Wave | |
| Voltage accuracy | Load balance 1%, Unbalance load 5% | |
| Waveform distortion rate (THD) | Linear load 2%, Nonlinear load 3% | |
| Dynamic Response | 5%,50ms( load 0 ~ 100%) | |
| Power Factor (PF) | 0.95 | |
| Inverter Efficiency | >94% | |
| Electrical insulation properties | 2000Vac, 1 Minute | |
| Running mode | Working continuously, can work 24h x 7 | |
| Start mode | Step down voltage start or variable frequency start | |
| Protection Function | Overload Ability | 120% - 35 seconds, 150% - 5 seconds |
| Protection | Input reverse polarity, under voltage, over voltage, output over-current,short circuit, overheating etc. | |
| Display | LCD | |
| Communication port | RS485(Optional) | |
| Cooling method | Fan-cooled | |
| Short-circuit protection | No automatic recovery, need to restart the machine | |
| Working environment | Degree of protection | IP20(indoor) |
| Working Altitude (m) | 2500m | |
| Working temperature | -15~+50 | |
| Relative humidity | 0~90% non-condensing | |
| Noise ( 1 meter) | 50dB | |
| Depth x Width x Height | 1200x1200x1860mm | |
| Weight (Kg) | 1300Kg | |
| Certification | European CE(EMC & LVD) | |