Parameters:
Model | SDP-250KW | |
Isolation mode | Low Frequency Transformer | |
DC Input | Rated voltage(Vdc) | 600V |
Input voltage range(V) | 540-850V | |
Rated current(A) | 416.7A | |
AC Output | Rated power(KW) | 250KW |
Rated voltage | 440VAC3% | |
Output phases | 3 phase + N + PE | |
Rated current (A) | 328A (phase current) | |
Output frequency | 50Hz or 60Hz | |
Output waveform | Pure Sine Wave | |
Voltage accuracy | Load balance 1%, Unbalance load 5% | |
Waveform distortion rate (THD) | Linear load 2%, Nonlinear load 3% | |
Dynamic Response | 5%,50ms( load 0 ~ 100%) | |
Power Factor (PF) | 0.95 | |
Inverter Efficiency | >94% | |
Electrical insulation properties | 2000Vac, 1 Minute | |
Running mode | Working continuously, can work 24h x 7 | |
Start mode | Step down voltage start or variable frequency start | |
Protection Function | Overload Ability | 120% - 35 seconds, 150% - 5 seconds |
Protection | Input reverse polarity, under voltage, over voltage, output over-current,short circuit, overheating etc. | |
Display | LCD | |
Communication port | RS485(Optional) | |
Cooling method | Fan-cooled | |
Short-circuit protection | No automatic recovery, need to restart the machine | |
Working environment | Degree of protection | IP20(indoor) |
Working Altitude (m) | 2500m | |
Working temperature | -15~+50 | |
Relative humidity | 0~90% non-condensing | |
Noise ( 1 meter) | 50dB | |
Depth x Width x Height | 1200x1200x1860mm | |
Weight (Kg) | 1300Kg | |
Certification | European CE(EMC & LVD) |