Technical Specification:
Model | SDP-12KW | ||||
Isolation mode | Low Frequency Transformer | ||||
DC Input | Rated voltage (Vdc) | 192V | 240V | ||
Rated current | 62.5A | 50A | |||
AC Output | Rated output power | 12KW | |||
Output waveform | Pure Sine Wave | ||||
Rated Voltage | 220VAC±3% | 120/240VAC ±3% | 380VAC ±3% | ||
Phases | Single phase | 2 phase 3 wire | 3 phase 4 wire | ||
Rated current | 55A | 50A (phase current) | 18A (phase current) | ||
Frequency | 50Hz or 60Hz | ||||
Rated output voltage range (V) | 110/120/220/230/240/380/400/415VAC optional | ||||
Power Factor | 0.95 | ||||
Overload Ability | 150%, 5 seconds | ||||
Efficiency | >94% | ||||
Waveform distortion rate (THD) | <3% Linear load | ||||
Dynamic Response (0 to 100% load) | 5% 50ms | ||||
Display | LCD | ||||
Running mode | Working continuously | ||||
Electrical insulation properties | 2000Vac, 1 Minute | ||||
Protection Function | Protection | Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc. | |||
Cooling method | Fan-cooled | ||||
Short-circuit protection | No automatic recovery, need to restart the machine | ||||
Working environment | Noise ( 1 meter) | 50dB | |||
Degree of protection | IP20 indoor | ||||
Working Altitude | 2000 | ||||
Working temperature | -25~+55 | ||||
relative humidity | 0~90% non-condensing | ||||
Mechanical dimension | Depth x Width x Height | 500 x 600 x 800mm | |||
Weight | 122Kg |