Single Phase 220VAC to 48VDC Battery Charger
Features:
Communication function
Main functions:
Set function
Communication function: Communicate with host controller through RS-485,to achieve parameter setup, working parameter inquiry and working condition control through communication.
Technical Specification:
| Model Items | 230D05ZZ-220AC | 230D10ZZ-220AC | 110D20ZZ-220AC | 110D10ZZ-220AC | |
| Output current(A) | 5 | 10 | 20 | 10 | |
| Power(KW) | 1.5 | 3.0 | 3.0 | 1.5 | |
| Input voltage range(VAC) | Min | 187 | |||
| Typical | 220 | ||||
| Max | 253 | ||||
| Output Adjustable Voltage rang(VDC) | Min | 190 | 95 | ||
| Typical | 220 | 110 | |||
| Max | 300 | 150 | |||
| voltage stabilization | +0.5% | ||||
| Charger efficiency(efficiency) | 93% | ||||
| Audible Noise max(dB) | 50 | ||||
| Storage temperature() | Min | -40 | |||
| Typical | 25 | ||||
| Max | 60 | ||||
| Working Conditions temperature() | Min | -10 | |||
| Typical | 25 | ||||
| Max | 40 | ||||
| uneven current in parallel operation | <3% | ||||
| Start delay (s) | 3S-8S | ||||
| Ripple factor | 0.5% | ||||
| Load grade | Continuous working with Grade I(100%) rating output current | ||||
| Automatic current limiting technology | The output current cannot increase infinitely. When output current exceed limited current value, a constant current output. The maximum output current value of each module is limited to the rated output. | ||||
| Output over voltage protection function | After output over voltage occurs(320+5VDC), the module locks up automatically | ||||
| output short circuit protection | When the output current get short circuit, the module will protect itself from broken. After | ||||
| Note: The constant Voltage Stabilization Tolerance does not contain the built-in isolating diode's influence. | |||||